FREECOOL-HD Intelligent Control Free Cooling Unit
Brief IntroductionFREECOOL-HD intelligent ventilation unit is applied in shelters and small data center. The unit introduces outdoor fresh air with lower temperature to cool equipment room. By using t
Top
information
Brief Introduction | |
FREECOOL-HD intelligent ventilation unit is applied in shelters and small data center. The unit introduces outdoor fresh air with lower temperature to cool equipment room. By using the FREECOOL unit, the running hours of other temperature control units can be highly reduced, achieving power energy saving around 30~90%. The FREECOOL-HD unit using EC fans can adjust the air volume automatically according to the temperature difference with the lowest power consumption. | FREECOOL-HD unit with large air volume, high cooling density and luxuriant control functions, can meet all the precision control requirement of temperature and cleanness in equipment room. FREECOOL-HD without refrigeration system realizes easy installation and convenient maintenance. The unit is available in 2 different air flow schemes: up flow and down flow, and 2 installation positions: outdoor and indoor, offering more options for different customers. |
Capacity | |
2400~21600 m3/h | |
Applications | |
Small to mid-size switching room for telecommunication Small to mid-size data center and computer room | UPS and battery room Industrial process control center |
Features | |
High energy efficiency Using the FREECOOL-HD unit, the running hours of other temperature control units can be highly reduced.
| Control to the other temperature control unit When the FREECOOL-HD unit can fully meet the cooling demand of base station, the controller can send a signal to stop the other temperature control unit in the site.
Completely auto protection
|
Options | |
G4 washable main air filter Pressure transducer Differential pressure switch for filter clogged Electric heater Supply air temperature Gravitational Pressure Relief Valve (air discharge) Electric motorized air discharge valve Electric motorized non-return valve Air inlet louver | Mounting plinth Head Blower RS232 communication interface card RS485 communication interface card Clock card Contactor for existing temperature control units (For existing temperature control units) Additional room temperature sensor Humidity sensor EC fan |
Model |
| 24F1 | 48F2 | 72F1 | 144F2 | 216F3 |
Supply air scheme |
| O/U | ||||
Air volume | m3/h | 2400 | 4750 | 7200 | 14400 | 21600 |
Air volume | m3/s | 0.67 | 1.3 | 2.0 | 4.0 | 6.0 |
Cooling capacity | ||||||
△t=5℃ | kW | 4.0 | 7.9 | 12.0 | 24.0 | 36.0 |
△t=10℃ | kW | 8.0 | 15.8 | 24.0 | 48.0 | 72.0 |
△t=12℃ | kW | 9.6 | 19 | 28.8 | 57.6 | 86.4 |
Power source |
| 230V/1/(50/60Hz) | 400V/3/(50/60Hz) | |||
Fan | ||||||
Type |
| Single inlet backward curved centrifugal fan | ||||
Qty. of fan | n. | 1 | 2 | 1 | 2 | 3 |
Input power | kW | 0.5 | 1.0 | 2.1 | 4.2 | 6.3 |
Current | A | 3.1 | 6.1 | 3.2 | 6.4 | 9.4 |
Width*Depth*Heigh | mm | 700*450*1320 | 1150*450*1320 | 850*800*1770 | 1650*800*1770 | 2450*800*1770 |
Weight | kg | 65 | 89 | 150 | 260 | 350 |